Product photo
Rack Mount Modular UPS 40KVA-50KVA
HQ-MR series rackmount modular UPS · online double conversion · scalable power modules.
Models: HQ-M40R / HQ-M50R
Rated capacity
40 kVA / 50 kVA
Power module
20 kVA / 25 kVA · Qty: 2
Efficiency
96% (double conversion) · >99% (ECO)
Display
5" LCD touch screen
| Parameter | Value |
|---|---|
| Model | HQ-M40R / HQ-M50R |
| Rated capacity | 40 kVA / 50 kVA |
| Power module capacity | 20 kVA / 25 kVA |
| Power module quantity | 2 |
| Input wiring method | 3 Phase + N + PE |
| Input rated voltage | 380/400/415 VAC (line-line) |
| Input rated frequency | 50/60 Hz |
| Input voltage range | 305–477 VAC (line-line) full load; 304–228 VAC (line-line) load derating linearly from 100% to 80% |
| Input frequency range | 40–70 Hz |
| Input power factor | > 0.99 |
| THDi | < 3% (linear full load) · < 5% (non-linear full load) |
| Bypass rated voltage | 380/400/415 VAC (line voltage) |
| Bypass voltage range | Factory setting -20% ~ +15%; settable upper: +10%, +15%, +20%, +25%; settable lower: -10%, -15%, -20%, -30%, -40% |
| Bypass frequency range | Settable ±0.5 Hz, ±1 Hz, ±2 Hz, ±3 Hz, ±10% (default) |
| Bypass overload capacity | 110% for long run; >150% for 200 ms |
| Battery voltage | ±192 VDC (360–528 VDC; 30–44 units settable, default: 32 units) |
| Output rated voltage | 380/400/415 VAC (line-line) |
| Output rated frequency | 50/60 Hz |
| Output power factor | 1 |
| Voltage accuracy | ≤ ±1.0% (balanced load) · ≤ ±5.0% (unbalanced load) |
| Frequency accuracy | 50/60 Hz ± 0.01% |
| Frequency tracking range | Settable ±0.5 Hz ~ ±5 Hz (default: ±3 Hz) |
| THDu | ≤ 2% (100% linear load) · ≤ 4% (nonlinear load) |
| Three-phase phase accuracy | 120° ± 1° |
| Crest factor | 3:1 |
| Overload | <105% long run; <110% 60 mins; 110–125% 10 mins; >125–150% 1 min; >150% 200 ms |
| System efficiency | 96% (double conversion mode) · >99% (ECO mode) |
| Wiring | Bottom in |
| Language | Chinese, English; optional: Russian, Italian, Spanish, German, etc. |
| Protection class | IP20 |
| Communication | RS232/RS485; optional: SNMP card / dry contact |
| Working condition | 0–40°C; 0–95% RH (no condensation) |
| Noise | < 60 dB @ 1 meter |
| Altitude | <1000 m no derating; >1000 m derating 1% per each 100 m |
| Cabinet type | 2 Modules |
| System size (W×D×H) | 482.6 × 800 × 353.2 mm (8U) |
| Module size (W×D×H) | 440 × 690 × 86 mm (2U) |
| System weight | 56 kg |
| Module weight | 24 kg (20 kVA) · 25 kg (25 kVA) |
| Minimum order | 60 |